7. Test run

7.1 Checking procedure before the test run

When you have finished the installation, perform the test run according to the following procedure. After performing the test
run, hand over the system to the customer.
Perform the test run of the indoor units one by one in order.
Make sure that the electrical wiring and the refrigerant piping are correctly connected.
Start the indoor units one by one in order to make sure that the indoor units are correctly numbered.
You should perform the test run according to
D A N G E R
• Do not operate the system until all the check points have been cleared.
• Measure the resistance between the ground and the terminal of the electrical components. Make sure that
the electrical resistance is more than 1 MΩ. Otherwise, do not operate the system until you find the electrical
leakage and you repair the electrical leakage. Do not impress the voltage on the terminals for transmission 1
and 2. (*)
• Pay attention to the following items while the system is running.
-
Do not touch any of the parts at the discharge gas side with your hands because the compressor chamber
and the pipes at the discharge gas side are hot at a temperature that is higher than 90 °C.
-
DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES). If you do, you will cause a serious accident.
Do not touch any electrical components for more than three minutes after turning OFF the main switch.
Checking procedure
1 Make sure that the stop valve of the gas line and the stop valve of the liquid line are fully open.
2 Make sure that there is no refrigerant leakage. The flare nuts sometimes loosen because of the vibration during the
transportation.
3 Make sure that the refrigerant piping and the electrical wiring belong to the same system. Make sure that the setting of
the unit number of DSW1, DSW6 and RSW1 of indoor units correspond to the system.
4 Make sure that the setting of the DIP switches on the printed circuit board of the indoor units and the outdoor units are
correct. Especially, pay attention to the setting of the lift between the indoor units and the outdoor units. Refer to chapter
4 "Electrical Wiring" for details.
5 Make sure that the switch on the main power source has been ON for more than twelve hours in order to warm the
compressor oil by means of the oil heater.
6 Check whether or not the electrical wiring of the indoor units and the outdoor units are connected as shown in chapter
4 "Electrical Wiring".
7 Make sure that each wire terminal (L1,L2,L3 and N or L1 and N) is correctly connected at the power source.
N O T E
Make sure that the field-supplied electrical components (main switch fuse, fuse-free breaker, earth leakage
breaker, wires, conduit connectors and wire terminals) have been properly selected according to the electrical
data in the technical catalogue of the unit. Also, make sure that the field-supplied electrical components com-
ply with the national codes and the local codes.
Use the shielded cables for the field wiring in order to avoid the electrical noise. (The length of the shielded
cable should be less than 1000 m. The size of shielded cable should comply with the local codes).
Make sure that the terminals for the power supply wiring ("L1" to "L1" and "N" to "N" of each terminal board
for AC 230 V and the terminals for the intermediate wires between the indoor unit and the outdoor unit (Ope-
rating Line: terminals of each terminal board for DC 12 V) match correctly. Otherwise, you may damage some
components.
• For RAS-12HN(P/C) units, the operation may not be available within 4 hours after turning ON the power supply
due to the unheated crankcase (stoppage code: d1-22). If the compressor should be within 4 hours, turn ON
the power and wait for more than 30 seconds. Press PSW1 and PSW3 on the outdoor PCB simultaneously for
more than 3 seconds. The forced thermo-OFF function (d1-22) is cancelled and the compressor operation is
available..
168
SMGB0079 rev.0 - 01/2013
Test run procedure using the remote control switch
on next pages.