10.3.2.13 Removing reversing valve
1  Remove the service cover, the bottom service cover, the rear cover and the upper cover following
cover,
Removing bottom service cover and rear cover
2  Recover the refrigerant from check joints according to
3  Remove the reversing valve coil according to
4  Remove the reversing valve assemblies from the fixed positions (5 brazing parts).
a.  Remove the reversing valve and the stop valve with cooling the valve bodies by wet cloth.
b.  Perform the brazing work with attention not to burn the electrical wirings and the piping insulations.
5  Remove reversing valve from the assemblies. (5 brazing parts) At this time, perform the brazing work with cooling the
reversing valve body by wet cloth.
6  When reassembling after replacing the reversing valves, perform in the reverse procedure of removing.
a.  Run the lead wires to be located to the original position, and fix them by the plastic band.
b.  Attach the crankcase heater according to
356
SMGB0079 rev.0 - 01/2013
and
Removing upper
Removing

Removing Reversing Valve

Removing
Compressor.
Brazing part
Brazing Part
(to heat exchanger)
(to Heat Exchanger)
Reversing valve
Reversing Valve
Brazing part
Brazing Part
(to Heat Exchanger)
(to heat exchanger)
Brazing part
Brazing Part
(to Accumulator)
(to accumulator)
Brazing part
Brazing Part
(Gas stop valve)
(for Gas Stop Valve)
Brazing part
Brazing Part
(for Discharge Pipe)
(discharge pipe)
cover.
Compressor.
Coil.
Removing service
5 brazing
parts

Hide quick links: