Hitachi RAS-2-HVNP Service Manual page 161

Utopia ivx premium / ivx standard h(v)n(p/c)(e) series
Table of Contents

Advertisement

6. Optional functions

 
Specification of the components for a correct installation
Component
Auxiliary relay (X3)
(SS1) (x1), (x2) contact example
3P connector cable
Wire (control
Voltage: 12V DC
Wire (power) Voltage: 230V
N O T E
• The connection of the input signal is only an example.
• Keep the CN1 and CN2 wires as short as possible.
• Do not run the wires along 230 V/400 V CA power cables separately install them at a distance of more than
30cm. (The cables may intersect.)
• If you install the wires along a power supply wire, insert the wires in a metal conduit tube and ground one end
of the tube.
• The maximum wiring length is 70 m. If you use this function, it is recommended that you use safety devices
such as an electrical leakage breaker or a smoke detector.
147
SMGB0079 rev.0 - 01/2013
Manufacturer or specifications
OMRON mini power relay model:
MY1F or equivalent
Manual type
Optional part PCC-1A (capable of con-
necting the JST XHP –3 connector)
0.5 mm²
2.0 mm²
Remarks
Voltage between relay terminals 12 Vdc - 75 mA
Voltage between terminals of the 230V - 5 mA contactor
Five wires with connectors as one set