Figure 41. Bypass Shunt Trip, Battery Shunt Trip And Detect Terminal Detail - Eaton 93PM-L Series Installation And Operation Manual

20 – 60 kw (208v)
Table of Contents

Advertisement

18. If removed, reinstall the sidecar front panel and secure with the retained hardware.
19. Close the UPS outside door and secure the latch.

Figure 41. Bypass Shunt Trip, Battery Shunt Trip and Detect Terminal Detail

Table 24. Shunt Trip and Battery Detect Connections and Wire Terminations
Terminal
Name
1
48 Vdc Bypass Shunt
Trip –
2
48 Vdc Bypass Shunt
Trip +
5
48 Vdc Battery Shunt
Trip –
6
48 Vdc Battery Shunt
Trip +
7
48 Vdc Battery Aux
1–A
8
48 Vdc Battery Aux
1–B
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
CN8
Description
Output: Contacts used to open
bypass breaker or disconnect
Output: Contacts used to open
battery breaker or disconnect
Output: Contacts used to open
battery auxiliary breaker or
disconnect
UPS System Installation
Recommend-
ed
Size of
Minimum
Pressure
Wire Size
Termination
Twisted Pair
Wires #18
#14 #30 AWG
AWG
Tightening
Torque
2 lb in
(0.22-0.25 Nm)