Figure 19. Shunt Trip, Battery Detect, And Thermal Sensor Wiring - Eaton 93pm Installation Manual

Table of Contents

Advertisement

Table 8. IBC TB2 Interface Wiring Terminal Block Terminations
Size of Pressure
Terminal Function
Termination
Shunt Trip
Battery Detect
Thermal Sensor

Figure 19. Shunt Trip, Battery Detect, and Thermal Sensor Wiring

Building
Alarm TB
10
9
8
7
6
5
4
Thermal
3
Sensor
2
Battery
1
Detect
UPS
Shunt
Trip TB
4
3
2
Shunt
Trip
1
UPS
Tightening
Torque Nm (lb
in)
#26–#16
0.4 (3.5) - 0.8 (7.1)
#26–#16
0.4 (3.5) - 0.8 (7.1)
#26–#16
0.4 (3.5) - 0.8 (7.1)
TB 2
TB 2
10
10
9
9
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
IBC1
IBC2
Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06
Type
Screw
Comments
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Use wire rated for 600V and Class 1 wiring
methods.
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
Slotted
Use #18 AWG twisted-pair wires for each input
and return or common. Strip wire insulation
back 10 millimeters to wire terminal blocks.
TB 2
10
9
8
7
6
5
4
3
2
1
IBC3
Installation
TB 2
10
9
8
7
6
5
4
3
2
1
IBC4
39

Advertisement

Table of Contents
loading

Table of Contents