Table 12. Eaton 93PM IBC-LW or Eaton 93PM IBC-LHW – TB2 Interface Connections (Continued)
Terminal TB2
2
1

Figure 24. Shunt Trip and Battery Detect Wiring

Building
Alarm TB
10
9
8
7
6
5
4
Thermal
Sensor
3
2
Battery
Detect
1
UPS
Shunt
Trip TB
4
3
2
Shunt
Trip
1
UPS
NOTE 1 IBC1 is closest to the UPS.
NOTE 2 The IBC shunt trip is wired in parallel. The IBC battery detect is wired in series.
NOTE 3 TB2 is located at the top of the IBC.
NOTE 4 If less than four IBCs are installed, the last IBC TB2-5 connection returns to UPS Building Alarm terminal.
NOTE 5 The Thermal Sensor is optional.