Table 6. IMM2 error messages (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
80070201-0301xxxx
Sensor CPU n
80070201-0302xxxx
OverTemp has
transitioned to critical
from a less severe
state.
(n = microprocessor
number)
80070301-0301xxxx
Sensor CPU n
80070301-0302xxxx
OverTemp has
transitioned to
non-recoverable from
a less severe state.
(n = microprocessor
number)
64
IBM System x3650 M4 Type 7915: Problem Determination and Service Guide
Error
A sensor has
changed to critical
state from a less
severe state.
Error
A sensor has
changed to
non-recoverable
state from a less
severe state.
1. Make sure that the fans are
operating, that there are no
obstructions to the airflow (front and
rear of the server), that the air
baffles are in place and correctly
installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature.
You must be operating within the
specifications (see "Features and
specifications" on page 7 for more
information).
3. Make sure that the heat sink for
microprocessor nis installed
correctly.
4. (Trained technician only) Replace
microprocessor n (see "Removing a
microprocessor and heat sink" on
page 279 and "Installing a
microprocessor and heat sink" on
page 282).
(n = microprocessor number)
1. Make sure that the fans are
operating, that there are no
obstructions to the airflow (front and
rear of the server), that the air
baffles are in place and correctly
installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature.
You must be operating within the
specifications (see "Features and
specifications" on page 7 for more
information).
3. Make sure that the heat sink for
microprocessor n is installed
correctly (see "Installing a
microprocessor and heat sink" on
page 282 for more information).
4. (Trained technician only) Replace
microprocessor n (see "Removing a
microprocessor and heat sink" on
page 279 and "Installing a
microprocessor and heat sink" on
page 282).
(n = microprocessor number)