Table 6. IMM2 error messages (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v If an action step is preceded by "(Trained technician only)," that step must be performed only by a trained
technician.
80010701-1403xxxx Numeric sensor
DIMM AB VR Temp
going high (upper
non-critical) has
asserted.
80010901-1403xxxx Sensor DIMM AB VR
Temp going high
(upper critical) has
asserted.
80010b01-1403xxxx Sensor DIMM AB VR
Temp going high
(upper
non-recoverable) has
asserted.
80010701-1404xxxx Sensor DIMM CD VR
Temp going high
(upper non-critical)
has asserted.
80010901-1404xxxx Sensor DIMM CD VR
Temp going high
(upper critical) has
asserted.
80010b01-1404xxxx Sensor DIMM CD VR
Temp going high
(upper
non-recoverable) has
asserted.
80010701-1405xxxx Sensor DIMM EF VR
Temp going high
(upper non-critical)
has asserted.
80010901-1405xxxx Sensor DIMM EF VR
Temp going high
(upper critical) has
asserted.
80010b01-1405xxxx Sensor DIMM EF VR
Temp going high
(upper
non-recoverable) has
asserted.
Warning
An upper
non-critical sensor
going high has
asserted.
Error
An upper critical
sensor going high
has asserted.
Error
An upper
non-recoverable
sensor going high
has asserted.
Warning
An upper
non-critical sensor
going high has
asserted.
Error
An upper critical
sensor going high
has asserted.
Error
An upper
non-recoverable
sensor going high
has asserted.
Warning
An upper
non-critical sensor
going high has
asserted.
Error
An upper critical
sensor going high
has asserted.
Error
An upper
non-recoverable
sensor going high
has asserted.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air from
exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air from
exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
1. Reduce the ambient temperature.
2. Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air
from exiting the server.
Check the server airflow. Make sure
that nothing is blocking the air from
coming into or preventing the air from
exiting the server.
Chapter 3. Diagnostics
49