NEC NEAX 2000IVS2 Installation Manual page 121

Integrated voice server
Hide thumbs Also See for NEAX 2000IVS2:
Table of Contents

Advertisement

3. Battery Replacement Table and Battery Warnings
The label which shows battery replacement table and battery warnings is attached to the
reverse side of Front Cover for PIM and BATTM.
During the battery installation process, the warning statements must be observed. When re-
placing batteries, the battery replacement table should be observed in order to increase bat-
tery life and insure a safe operation.
PIM/BATTM
BATTERY REPLACEMENT TABLE
INSTALLATION DATE:
AMBIENT
5 ~ 35°C
TEMPERATURE
(AVERAGE 25°C)
REPLACEMENT
3 YEARS
INTERVAL
o ELECTROLYTE LEAKAGE OR OTHER HAZARDS
MAY RESULT IF THE BATTERY IS NOT REPLACED
IN ACCORDANCE WITH THE SPECIFIED INTER-
VALS.
2
NEAX2000 IVS
Installation Procedure Manual
ND-70928 (E), Issue 1.0
CAUTION
0 ~ 50°C
0 ~ 50°C
(AVERAGE 25°C)
(AVERAGE 40°C)
2 YEARS
1 YEAR
CHAPTER 2 INSTALLATION
LABEL
FRONT COVER
TO PREVENT INJURY AND SKIN BURN,
CAUTION
PAY ATTENTION TO THE FOLLOWING.
o DO NOT STRIKE A MATCH OR CAUSE A SPARK IN
VICINITY OF BATTERY.
o PLACE THE EQUIPMENT WELL VENTILATED
AREA.
o DO NOT SHORT.
o REPLACE BATTERY ONLY AFTER BATTERY
GASES HAVE BEEN DISPERSED.
Battery Connection
Page 95