Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
Group 3 Analog Input/Output Parameters
03-00
Analog Input 1 (VR)
Analog Input 2 (ACI)
03-01
Analog Input 3 (AVI)
03-02
0: No function
1: Frequency command (torque limit under TQR
control mode)
2: Reserved
3: Preload input
4-6: Reserved
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
When it is frequency command or TQR speed limit, the corresponding value for 0~±
10V/4~20mA is 0 – max. output frequency(Pr.01-00)
When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is
0 – max. output torque (Pr.07-14).
When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 – rated
torque.
4-58
Settings
This parameter can be set during operation.
VF
VFPG
Revision May 2009, 00DE, V0.50
Factory Setting: 1
Factory Setting: 0
Factory Setting: 0
FOCPM