Delta BLD-E1 Series User Manual page 113

Brushless motor dc drive
Table of Contents

Advertisement

Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
Group 7 Special Parameters
Reserved
07-00
Reserved
07-01
DC Brake Current Level
07-02
Control
VF
VFPG
mode
Settings
This parameter sets the level of DC Brake Current output to the motor during start-up and
stopping. When setting DC Brake Current, the Rated Current (Pr.00-01) is regarded as 100%.
It is recommended to start with a low DC Brake Current Level and then increase until proper
holding torque has been attained.
When it is FOCPM mode, it can enable DC brake function by setting to any value.
DC Brake Time during Start-up
07-03
Control
VF
VFPG
mode
Settings
This parameter determines the duration of the DC Brake current after a RUN command.
DC Brake Time during Stopping
07-04
Control
VF
VFPG
mode
Settings
This parameter determines the duration of the DC Brake current during stopping.
Start-Point for DC Brake
07-05
Control
VF
VFPG
mode
Settings
This parameter determines the frequency when DC Brake will begin during deceleration.
When the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin
from the min. frequency.
4-72
0 to 100%
FOCPM
0.0 to 60.0 sec
FOCPM
0.0 to 60.0 sec
0.00 to 48000rpm
This parameter can be set during operation.
Revision May 2009, 00DE, V0.50
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 0