Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
Group 6 Protection Parameters
Low Voltage Level
06-00
Control
VF
VFPG
mode
Settings 230V series 160.0~220.0Vdc
460V series 320.0~440.0Vdc
It is used to set the Lv level.
Phase-loss Protection
06-01
Control
VF
VFPG
mode
Settings
It is used to set the phase-loss treatment. The phase-loss will effect drive's control
characteristic and life.
Over-Current Stall Prevention during Acceleration
06-02
Control
VF
VFPG
mode
Settings
During acceleration, the AC drive output current may increase abruptly and exceed the value
specified by Pr.06-02 due to rapid acceleration or excessive load on the motor. When this
function is enabled, the AC drive will stop accelerating and keep the output frequency
constant until the current drops below the maximum value.
4-64
FOCPM
input voltage
Pr. 06-00
FOCPM
0
Warn and keep operation
1
Warn and ramp to stop
2
Warn and coast to stop
00: disable
00~250%
This parameter can be set during operation.
30V(60V)
LV
Factory Setting: 180.0
Factory Setting: 360.0
Factory setting: 2
Factory setting: 00
Revision May 2009, 00DE, V0.50