06-02
Over-Current
Detection
Level
Over-current Stall Prevention during Operation
06-03
Control
VF
VFPG
mode
Settings
If the output current exceeds the setting specified in Pr.06-03 when the drive is operating, the
drive will decrease its output frequency by Pr.06-04 setting to prevent the motor stall. If the
output current is lower than the setting specified in Pr.06-03, the drive will accelerate (by
Pr.06-04) again to catch up with the set frequency command value.
Accel./Decel. Time Selection of Stall Prevention at constant speed
06-04
Control
VF
VFPG
mode
Settings
Revision May 2009, 00DE, V0.50
actual acceleration time when over-current stall
prevention is enabled
00: disable
00 to 250%
Over-Current Stall
Prevention during
Operation, output
Over-Current
frequency decrease
Detection Level
06-03
over-current stall prevention during operation
0
by current accel/decel time
1
by the 1st accel/decel time
2
by the 2nd accel/decel time
3
by the 3rd accel/decel time
4
by the 4th accel/decel time
5
by auto accel/decel time
Chapter 4 Parameters| BLD-E1 Series
Over-Current Stall
prevention during
Acceleration,
frequency held
Output Current
Output
Frequency
current
Output
Frequency
time
Factory setting: 00
Time
Factory setting: 0
4-65