Temperature And Humidity Requirements; Input Power And Insulation Performance Specifications; Table 2.8 Environmental Specifications; Table 2.9 Input Power And Insulation Performance Specifications For Rack-Mount Model - Acer HDS AMS200 Reference Manual

Acer hds ams200 server: reference guide
Table of Contents

Advertisement

2.4.2

Temperature and Humidity Requirements

Table 2.8 lists the temperature and humidity requirements for the AMS200 subsystem.
Table 2.8
Environmental Specifications
Item
Temperature
Humidity
Altitude
2.4.3

Input Power and Insulation Performance Specifications

The following tables list the input power and insulation performance specifications for the
AMS200 rack-mount models and the AMS200 floor model.
Conductors shall be provided with 30 A over current protection in accordance with Article
240 of the National Electrical Code, ANSI/NFPA 70, and the Canadian Electrical Code, Part 1,
CSA C22.1, Section 14.
Table 2.9
Input Power and Insulation Performance Specifications for Rack-Mount Model
Item
Input power
specification
Insulation
performance
Note 1: Power current of Nx2 described above is required for operation by a single power supply unit.
Note 2: It indicates the current consumption in the usual state. When a power supply failure occurs, the power
consumption is provided by the single power supply for the subsystem.
32
Chapter 2 Planning for Installation and Operation
In operation (°C)
In non-operation (°C)
In transport/storage (°C)
Temperature change rate (°C/h)
In operation (%)
In non-operation (%)
Maximum wet bulb temperature (°C)
In operation (m)
In non-operation (m)
Model
Input voltage (V)
Frequency (Hz)
Number of phases, cabling
Steady-state current (A) (Note1) (Note2)
Breaking current (A)
Required power
Steady state (VA)
Starting state (VA)
Heat value (kJ/h)
Insulation withstand voltage
Insulation resistance
Specification
10 to 40
-10 to 50
-30 to 60
10 or less
8 to 80
8 to 90
29 (non-condensing)
-300 to 3,000
-300 to 12,000
Rack-Mount Model
RKS
RKAJ
AC 100/200 (100-120/200-240)
50/60 ± 1
Single-phase with protective grounding
4.0×2/2.0×2
2.6×2/1.3×2
16.0
10.0
800 or less
520 or less
800 or less
560 or less
2,880 or less
1,875 or less
AC 1,500 V (10 mA, 1 min)
DC 500 V, 10 M Ω or more
RKAJAT
2.4×2/1.2×2
480 or less
480 or less
1,730 or less