Operations from the Edit Device Parameters Window

5-2

Operations from the Edit Device Parameters Window

5-2-1

Preparing the Configurator Connection

Configurator Connected Using a DeviceNet Interface Board (Card)
1,2,3...
Master Connected using Serial Line
1,2,3...
5-2-2

Edit Device Parameters Window

1,2,3...
If problems occur in the connection with the Configurator, change the settings
for the master. Problems will occur if the master's message timeout time is too
short or the I/O size allocated in the master is different from that allocated in
the DeviceNet Communications Unit.
1. Right-click the icon for the master, then select Monitor to display the Mon-
itor Device Window.
2. Click the Stop Remote I/O Communication Button to stop remote I/O
communications with the DeviceNet Communications Unit.
Note This operation is not required if no error has occurred in the master node.
1. Double-click the icon for the master to display the Edit Device Parameters
Window and click the Message Timer Tab.
2. Double-click the unit number of the DeviceNet Communications Unit, set
5,000 ms in the Setup Message Timer Window, and execute download.
1. Turn ON the power to the DeviceNet Communications Unit and master,
and then put the Configurator online, and select Upload from the Network
Menu.
The configuration of Units connected in the Network will be read and dis-
played in the Network Configuration Window.
Section 5-2
71