Examples Using CompoWay/F Commands
Command Details
Response (Operation1)
98
[CMND S D C]
S
D01000+0: 2801 hex
+1: 0036 hex
+2: 0086 hex
+3: 0001 hex
+4: 0000 hex
+5: 0001 hex
+6: 02C1 hex
+7: 0003 hex
+8: 0000 hex
+9: 0100 hex
+10: 0002 hex
+11: 4000 hex
D
D01200:
C
D01100+0: 0017 hex
+1: 0010 hex
+2: 0000 hex
+3: 3FFE hex
+4: 0000 hex
+5: 0064 hex
D01200+0: 2801 hex
+1: 0000 hex
+2: 0009 hex
+3: 00B6 hex
+4: 0000 hex
+5: 0001 hex
+6: 0200 hex
+7: 0000 hex
Command code
DeviceNet Communications Unit node address = 00
Service code = 36 hex
Class ID = 0086 hex
Instance ID = 01 hex
E5ZN unit number = 00 hex, sub-address (fixed) =
00 hex
SID (fixed) = 00 hex MRC = 01 Hex
SRC = 02 hex, variable type = C1 hex
Write start address = 0003 hex (2 bytes)
Bit position (fixed) = 00 hex, No. of elements = 00
hex (2 bytes)
No. of elements = 01 hex, Data = 00 hex (4 bytes)
Data = 0002 hex
Data = 40 hex
First response storage word
No. of command data bytes
No. of response data bytes
Remote (destination) network address = 0
Remote (destination) node address = 3F hex
Remote (destination) Unit address = FE hex (10 hex
also possible)
Response required, communications port No.0, No.
of retries = 0 hex
Response monitoring time
Command code
End code (FINS)
No. of bytes received
Node address = 00 hex, Service code = B6 hex
E5ZN unit number = 00 hex, Sub-address (fixed) = 00 hex
End code (CompoWay/F) = 00 hex, MRC = 01 hex
SRC = 02 hex, End code (FINS-mini) = 00 hex (2 bytes)
End code (FINS-mini) = 00 hex