Allocating Data in the Master
64
Example: When Use COS Connection is selected.
The output for the Poll connection and the output for the COS or Cyclic
connection are sent in the same frame. Therefore, the same output size
must be set for both connections when using a Poll and COS combination,
or a Poll and Cyclic combination. When a COS or Cyclic connection are
used, always set a dummy output size, and set the same connection path
that is used for the Poll connection.
3. Click the OK Button, and return to the master's Edit Device Parameters
Window. Click the I/O Allocation (IN) Tab and edit the I/O allocations. In
the Edit I/O Allocate Window, the allocated words can be set for each con-
nection.
4. Click the OK Button, and return to the master's Edit Device Parameters
Window.
5. Select the General Tab, and click the Download Button to write the set I/O
memory allocations to the master.
6. Always click the OK Button to exit the master's Edit Device Parameters
Window. If the Cancel Button or the
be invalid.
Section 4-4
Button is clicked, the settings will