Allocating Data in the Master
Setting from the DeviceNet Configurator
1,2,3...
The default connections and connection paths are shown in the following
table.
Allocated Area
IN Area 1
Poll
OUT Area1
Poll
IN Area2
None
By setting the following connections as user-defined settings, the IN Area can
be divided into two areas.
Allocated Area
IN Area 1
Poll
OUT Area1
Poll
IN Area2
COS or Cyclic
1. In the Edit Device Parameters Window for the master, select the Unit in the
General Tab Page, and click the Advanced Setup Button, and then click
the Connection Tab.
Note
If the Auto allocation as is registered item is selected on the mas-
ter's General Tab Page, a message will be displayed when the con-
nection path is set indicating that the connection has been
changed, causing the current I/O allocations to be cleared. When
setting DeviceNet Communications Unit allocations automatically,
reselect this item after setting a connection.
2. Select User Setup, and select Use Poll Connection for one connection,
the same as the default setting. Then select the connection path from the
pull-down menu as Out Area 1 for the OUT side, and In Area 1 for the IN
side.
For the second connection, select either Use COS Connection or Use
Cyclic Connection, then select In Area 2 as from the pull-down menu on
the IN side as the connection path. For the connection path on the OUT
side, always set the same connection path as specified for the Poll connec-
tion.
Connection type used
Connection type used
Section 4-4
Connection path used
IN Area 1
OUT Area 1
None
Connection path used
IN Area 1
OUT Area 1
IN Area 2
63