Function And Performance Specifications - Omron E5ZN-DRT Operation Manual

Devicenet communications unit for e5zn temperature controllers
Hide thumbs Also See for E5ZN-DRT:
Table of Contents

Advertisement

Specifications
Item
Communications distance
Communications power supply
Maximum number of nodes that can be
connected
Maximum number of slaves that can be
connected
Error control
Power supply
1-2-2

Function and Performance Specifications

Item
Maximum number of Temperature
Controllers that can be connected
Applicable Temperature Control-
lers
Power supply
Copying
10
Baud rate
500 kbps
250 kbps
125 kbps
The values in parentheses apply when Thin Cables are used.
11 to 25 VDC
64 (includes Configurator when used.)
63
CRC error detection
Power supplied from DeviceNet communications connector (DeviceNet commu-
nications power supply and DeviceNet Communications Unit internal circuit
power supply)
Note
1. When a CS/CJ-series DeviceNet Unit is used as the master, two blocks
can be used for the IN Area (the connections can also be set). When a
CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is used, the
IN Area must be in 1 block, and up to 100 words (200 bytes) are allocated.
(Only polling connections can be used.)
2. When a CVM1, CV-series, or C200HX/HG/HE DeviceNet Master Unit is
used, up to 32 words can be allocated in the master for a single node.
3. The set points, alarm setting values, PID constants, and other Tempera-
ture Controller parameters can be set together.
16
• E5ZN-2QNH03TC-FLK
• E5ZN-2QPH03TC-FLK
• E5ZN-2TNH03TC-FLK
• E5ZN-2TPH03TC-FLK
• E5ZN-2CNF03TC-FLK
• E5ZN-2CPF03TC-FLK
Power supplied from Terminal Unit terminal block (terminals 19 and 20) (Communica-
tions power supply between DeviceNet Communications Unit and Temperature Con-
troller, and internal circuit power supply of Temperature Controller)
The parameters of the connected Temperature Controllers can be uploaded or down-
loaded as a batch, merely by manipulating the DIP switch on the front panel of the
DeviceNet Communications Unit.
The uploaded parameters are stored in the DeviceNet Communications Unit.
Specifications
Network length
Drop line length
100 m max.
6 m max.
(100 m max.)
250 m max.
6 m max.
(100 m max.)
500 m max.
6 m max.
(100 m max.)
Specifications
• E5ZN-2QNH03P-FLK
• E5ZN-2QPH03P-FLK
• E5ZN-2TNH03P-FLK
• E5ZN-2TPH03P-FLK
• E5ZN-2CNF03P-FLK
• E5ZN-2CPF03P-FLK
Section 1-2
Total drop line
length
39 m max.
78 m max.
156 m max.

Advertisement

Table of Contents
loading

Table of Contents