Examples Using CompoWay/F Commands
Program Example (Operation 1)
A20011
000000
First Scan
Flag ON
BSET(071)
Sets 0000 in D1000 to D1209.
# 0000
D1000
D1209
MOV(021)
Sets 2801 in D1000. (Command code = 2801)
# 2801
D1000
MOV(021)
Sets 0036 in D1001.
(Slave node address = 00, ServiceCode = 36)
# 0036
D1001
MOV(021)
Sets 0086 in D1002. (ClassID = 86)
# 0086
D1002
MOV(021)
Sets 0001 in D1003. (InstanceID = 01)
# 0001
D1003
Sets 0000 in D1004.
MOV(021)
(E5ZN Unit No. = 00, sub-address = 00)
# 0000
D1004
MOV(021)
Sets 0001 in D1005. (SID = 00, MRC = 01)
# 0001
D1005
MOV(021)
Sets 02C1 in D1006. (SRC = 02, variable type = C1)
# 02C1
D1006
MOV(021)
Sets 0003 in D1007. (Write address = 0003)
# 0003
D1007
MOV(021)
Sets 0000 in D1008.
(Bit position = 00, No. of elements = 00)
# 0000
D1008
MOV(021)
Sets 0100 in D1009. (No. of elements = 01, data = 00)
# 0100
D1009
Sets 0002 in D1010. (data = 0002)
MOV(021)
# 0002
D1010
MOV(021)
Sets 4000 in D1011. (data = 4000)
# 4000
D1011