Initial Temperature Controller Settings

1-3-5

Temperature Controller Registration

1,2,3...
1-4

Initial Temperature Controller Settings

Transferring
Temperature
Controller Parameters
Together
Setting with E5ZN-
SDL Setting Display
Unit
The unit numbers of the connected Temperature Controllers must be regis-
tered in the configuration in the DeviceNet Communications Unit. The
DeviceNet Communications Unit automatically verifies that the registered unit
numbers match the numbers of the Controllers currently able to communicate.
If the unit numbers do not match in the verification process, the Temperature
Controllers will be determined to have an error, causing the following status.
• The TS indicator will flash red.
• The Communicating Flag will turn OFF and the Communications Error
Flag will turn ON for each Temperature Controller that is not communicat-
ing but is registered as being connected to the DeviceNet Communica-
tions Unit.
The following two methods can be used to register the connection configura-
tion of the Temperature Controller.
1. Registering with the Configurator or explicit messages (Turn OFF pin 1 on
the DIP switch on the rear of the DeviceNet Communications Unit to en-
able this method)
2. Registering with the rotary switches on the rear of the DeviceNet Commu-
nications Unit (Turn ON pin 1 on the DIP switch on rear of the DeviceNet
Communications Unit to enable this method.)
The following four methods are provided for setting the E5ZN Temperature
Controllers.
Set each of the Temperature Controller parameters in the Edit Device Param-
eters Window from the DeviceNet Configurator, and then transfer them
together via the DeviceNet network.
Edit device parameters
Edit Unit parameters
Proportional band
Target value
Set the parameters from the E5ZN-SDL Setting Display Unit.
E5ZN-SDL Setting Display Unit
Terminal Unit connected to DeviceNet
Communications Unit
+
Configurator
CS/CJ-series DeviceNet Unit
Temperature
Controller
parameters
DeviceNet
Communications Unit
Section 1-4
PLC
DeviceNet
13