Operations from the Edit Device Parameters Window
Setting Method
1,2,3...
5-2-5

Setting the Unit Conduction Time Monitor

Setting Method
1,2,3...
74
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the General Tab, and enter the desired value in the Network
Power Voltage field.
The DeviceNet Communications Unit can record the conduction time (time
that communications power is supplied to the Unit), and when the value
exceeds the set monitor value, the Unit Maintenance Bit in the Unit Status
Area will be turned ON.
This function provides a guideline for when to replace the Unit.
Measuring unit: 0.1 h
Measured time: 0 to 429496729.5 h
Monitor value setting range: 0 to 429496729 hours (specify as an integer)
The present value for conduction time and the Unit Status Area can be
checked in the Maintenance Information Window when using Maintenance
Mode.
Note The present value and monitor value for the conduction time are held even
when the power is turned OFF.
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the General Tab, and enter the desired value in the Unit Conduc-
tion Time field.
(stored data: 00000000 to FFFFFFFF hex)
Section 5-2