Communications Parameters - Omron E5AN User Manual

Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

J Communications
parameters
Parameter
Communications unit No.
Baud rate
Communications data length
Communications stop bit
Communications parity
F Communications
parameter setup
Communications unit No.
Baud rate
Communications data
length
Communications stop bit
Communications parity
E5AN/EN
The E5AN/EN/CN/GN's communications specifications are set in the
communications setting level. These parameters are set on the E5AN/EN/
CN/GN's front panel.
The following table shows the communications parameters and their set-
ting ranges.
Displayed
Setting Range
Characters
0 to 99
1.2 / 2.4 / 4.8 / 9.6 / 19.2 (kbps)
7 / 8 (bit)
1 / 2
None / even / odd
Before you carry out communications with the E5AN/EN/CN/GN, set up
communications unit No., baud rate and other parameters by carrying out
the following procedure. For details of operations other than communica-
tions parameter setup, refer to the E5AN/EN/CN/GN User's Manuals.
(1) Hold down the
"operation level" to the "initial setting level."
(2) Press the
key for less than one second to move from the "initial
setting level" to the "communications setting level."
(3) Select the parameters as shown below by pressing the
(4) Use the
or
Communications unit No.
Baud rate
Communications data length
Communications stop bit
Communications parity
E5CN
0,
1
to 99
1.2 / 2.4 / 4.8 /
7
/ 8 (bit)
1 /
2
Highlighted characters indicate defaults.
key for at least three seconds to move from the
keys to change the parameter set values.
1.1 Outline
Set Value
9.6
/ 19.2 (kbps)
/
/
key.
Communications unit No.
Baud rate
Communications data length
Communications stop bit
Communications parity
E5GN
1--5

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5enE5cnE5gn

Table of Contents