Rear Panel Dip Switch - Omron E5ZN-DRT Operation Manual

Devicenet communications unit for e5zn temperature controllers
Hide thumbs Also See for E5ZN-DRT:
Table of Contents

Advertisement

Part Names and Functions

Rear Panel DIP Switch

Setting Simple I/O
Allocation
Setting I/O Allocations
from the Configurator
Rear Panel Rotary Switch
I/O allocation setting switch
Not used (leave set to OFF).
Use the rear panel DIP switch to set the Unit connection configuration and I/O
allocation to either simple I/O allocation or I/O allocation from the Configura-
tor.
Pin 1
OFF
I/O allocation set from the Configurator
ON
Simple I/O allocation setting
Use the rear panel rotary switch to set the highest unit number of the Temper-
ature Controllers connected to the DeviceNet Communications Unit. The con-
nection configuration will be automatically created and the I/O will be
automatically allocated for this setting.
With simple I/O allocation, when the DeviceNet Communications Unit is
started, it checks the communications status with the Temperature Controllers
up to the Temperature Controller with the highest unit number (power must be
supplied to the Terminal Unit). After checking the communications status, the
Temperature Controllers that are communicating normally are registered in
the connection configuration. IN and OUT Areas for Temperature Controller
data can also be allocated for the total number of connected Temperature
Controllers.
The Configurator can be used to allocate I/O and set the connection configu-
ration in the DeviceNet Communications Unit. The settings are recorded in the
non-volatile memory of the DeviceNet Communications Unit, so by setting
only once, the same settings can be used the next time they are required (the
connection configuration and I/O allocations are not set as factory settings.)
For details on simple I/O allocation, and setting I/O allocations with the Con-
figurator, refer to SECTION 4 Remote I/O Communications.
Note
1. Always turn OFF the DeviceNet communications power supply and Termi-
nal Unit power supply before performing setting operations.
2. Pin 2 must always be OFF.
3. When pin 1 is OFF (I/O allocations set from the Configurator), if the con-
nection configuration is not registered the MS indicator will flash green.
When the connection configuration is set from the Configurator, the De-
viceNet Communications Unit will automatically be reset and after starting
normally, the MS indicator status will be lit green.
4. Pins 1 and 2 are both OFF as the factory setting.
C
Highest unit number connected
4
Use this switch to set the highest unit number of the connected Temperature
Controllers. This setting is enabled when pin 1 of the rear panel DIP switch in
ON (simple I/O allocation) only.
I/O allocation setting switch
Section 3-1
25