Setting And Monitoring Temperature Controller Channels - Omron E5ZN-DRT Operation Manual

Devicenet communications unit for e5zn temperature controllers
Hide thumbs Also See for E5ZN-DRT:
Table of Contents

Advertisement

Sending Explicit Messages
6-5-4

Setting and Monitoring Temperature Controller Channels

Explicit
Read
message
/write
Tempera-
Read Reads the monitor
ture Con-
mode for maintenance
troller
information of the Tem-
Channel
perature Controller unit
Mainte-
number and channel
nance Infor-
(see note 1) specified
mation
by the Instance ID (1 to
Monitor
32).
Mode
Write Writes the monitor
mode for maintenance
information of the Tem-
perature Controller unit
number and channel
(see note 1) specified
by the Instance ID (1 to
32).
Set Value
Read Reads the set value
for Unit
(monitor value) for the
Conduction
Unit conduction time or
Time or
total RUN time (unit: s)
Total RUN
of the Temperature
Time
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
Write Writes the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
Unit Con-
Read Reads the PV for the
duction
Unit conduction time or
Time or
total RUN time (unit: s)
Total RUN
of the Temperature
Time Read
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
Monitor
Read Reads the monitor sta-
Status of
tus for the Unit conduc-
Unit Con-
tion time or total RUN
duction
time (unit: s) of the
Time or
Temperature Control-
Total RUN
ler unit number and
Time Read
channel (see note 1)
specified by the
Instance ID (1 to 32).
106
Function
Service
code
0E hex
10 hex
0E hex
10 hex
0E hex
0E hex
Note The following table shows the relationship between the Instance IDs (01 to 31)
and the Temperature Controller unit numbers (0 to 15) and channels (1 and
2).
Command
Class ID Instance
Attribute
ID
ID
7A hex
01 to 20
65 hex
hex
7A hex
01 to 20
65 hex
hex
7A hex
01 to 20
68 hex
hex
7A hex
01 to 20
68 hex
hex
7A hex
01 to 20
66 hex
hex
7A hex
01 to 20
67 hex
hex
Section 6-5
Response
Data size
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
1 byte
00 hex: Within
range
01 hex: Out of
range (monitor
value
exceeded)