Setting Devicenet Communications Unit Comment - Omron E5ZN-DRT Operation Manual

Devicenet communications unit for e5zn temperature controllers
Hide thumbs Also See for E5ZN-DRT:
Table of Contents

Advertisement

Operations from the Edit Device Parameters Window
!Caution Always turn OFF the Output Enable Bits when using the Configurator to
5-2-3

Setting DeviceNet Communications Unit Comment

72
2. Double-click the icon for the DeviceNet Communications Unit in the Net-
work Configuration Window, or right-click and select Parameter and Edit
to display the Edit Device Parameters Window for the DeviceNet Commu-
nications Unit.
Note
1. Click the Upload Button to read the Unit configuration registered in the De-
viceNet Communications Unit.
2. Click the Upload Real Configuration Button to read the configuration of the
Temperature Controllers currently connected to the DeviceNet Communi-
cations Unit at that time.
3. Click the Reset Button to reset the DeviceNet Communications Unit. The
status of the Unit will be the same as if the power had been turned OFF
and ON again.
4. Click the Default Setting Button to initialize all the DeviceNet Communica-
tions Unit settings, and return them to the factory setting status. The Con-
figurator screen will not return to factory setting status, however, so click
the Upload Button to read the settings again.
download the parameters set in the Temperature Controller. If the Output
Enable Bits are not OFF when downloading, the set values allocated with I/O
and the set values downloaded with the Configurator will compete, causing
the set values allocated using I/O to be enabled. For details on Output Enable
Bits, refer to Output Enable Bits (Type Number 1, 2) on page 58.
A name can be assigned to the DeviceNet Communications Unit and
recorded in the Unit. The name can be entered using up to 32 standard char-
acters. The comment for the registered DeviceNet Communications Unit is
used in the Configurator display, such as in the Maintenance Mode Window
(refer to page 83).
Note The DeviceNet Communications Unit comment is stored even when the
power is turned OFF.
Section 5-2