Wiring The Power Supply - Omron E5ZN-DRT Operation Manual

Devicenet communications unit for e5zn temperature controllers
Hide thumbs Also See for E5ZN-DRT:
Table of Contents

Advertisement

Wiring the Terminal Unit
Crimp Terminals
3-3-2

Wiring the Power Supply

UL/CSA Safety Standards
30
Note
1. Wire the signal lines separately from power lines to prevent noise interfer-
ence.
2. Use crimp terminals for wiring.
Always connect M3 crimp terminals, as shown below, when wiring the Termi-
nal Unit. Tighten to a torque of 0.40 to 0.56 N·m.
5.8 mm max.
Connect the power supply (20.4 to 26.4 VDC) for the Temperature Controllers
to terminals 19 and 20, as shown in the following diagram.
When more than one block of Temperature Controllers is used, connect a
power supply to the E5ZN-SCT24S Terminal Unit on the leftmost side of each
block.
+
19
Power supply
24 VDC
20
Note This power supply is used for communications between the DeviceNet Com-
munications Unit and the Temperature Controllers (RS-485), and to start the
Temperature Controllers.
Consider the power consumption of each Temperature Controller and the con-
nected I/O when selecting a power supply.
When reinforced insulation is required, connect the I/O to a device without an
exposed charged section or to a device with basic insulation that is suitable for
the maximum usage voltage of the I/O section.
Use a SELV power supply with overcurrent protection.
A SELV power supply has redundant I/O or increased insulation, an output
voltage of 30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-05024CD (OMRON) or S8VS-06024A
(OMRON)
5.8 mm max.
19
13
7
1
20
14
8
2
21
15
9
3
22
16
10
4
23
17
11
5
24
18
12
6
E5ZN-SCT24S
Section 3-3