3-4
Procedures after Turning ON the
Power Supply
3-4-1
Basic Flow of Operations
The basic flow of operations after you turn ON the power supply is shown below.
3-4-2
Basic Procedure
The basic procedure is given below.
1
Turn ON the power supply.
Operation Level
2
Set the input type.
Press the O (Level) Key
for at least 3 seconds.
Press the U (Up) and
D (Down) Keys to
change the value.
When you are finished, press the O (Level) Key for at least 1 second to return to the operation display.
E5@C Digital Temperature Controllers User's Manual (H174)
1. Turn ON the power supply.
↓
2. Set the input type.
↓
3. Set the control method.
↓
4. Set the alarm type.
↓
5. Set the set point.
↓
6. Set the alarm set values.
25
s.err
0
25
0
Initial Setting Level
in-t
5
Initial Setting Level
in-t
0
3 Part Names and Basic Procedures
s.err (input error) flashes on the display
if a sensor is not connected or if the
0
connected sensor is different from input
type. Connect a sensor if one is not
already connected.
The display flashes.
in-t (IN-T) will be displayed to show that the Initial
Setting Level has been entered.
The default setting is 5
(5: K thermocouple at −200 to 1,300 °C).
in-t (IN-T): Indicates the Input Type parameter.
Input Type: 0
(Pt100 resistance thermometer at −200 to 850 °C) (example)
3
3 - 11