Remote I/O Terminals with Transistors
5-5-7
Remote I/O Terminals with 8 Transistor Inputs and 8 Transistor
Outputs: DRT2-MD16 (NPN) and DRT2-MD16-1 (PNP)
Input Specifications
Output Specifications
Component Names and Functions: DRT2-MD16 and DRT2-MD16-1
Item
Model
DRT2-MD16
Internal I/O common NPN
Input points
8 points
ON voltage
15 V DC min.
(between each input terminal
and V)
OFF voltage
5 V DC max.
(between each input terminal
and V)
OFF current
1 mA max.
Input current
6.0 mA max./point (for 24 V DC)
3.0 mA min./point (for 17 V DC)
ON delay time
1.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits
8 points with one common
Item
Model
DRT2-MD16
Internal I/O common NPN
Output points
8 points
Rated output current 0.5 A/point, 4.0 A/common
Residual voltage
1.2 V max.
(at 0.5 A between each output
terminal and G)
Leakage current
0.1 mA max.
ON delay time
0.5 ms max.
OFF delay time
1.5 ms max.
Number of circuits
8 points with one common
Communications
connector
Specifications
DRT2-MD16-1
PNP
15 V DC min.
(between each input terminal
and G)
5 V DC max.
(between each input terminal
and G)
Specifications
DRT2-MD16-1
PNP
1.2 V max.
(at 0.5 A between each output
terminal and V)
0.1 mA max.
Rotary switches
Used to set node address.
DeviceNet
Input indicators
indicators
Indicate the input status of each contact.
MS NS
NODE ADDRESS
0
1
2
3
4
5
5
5
IN
X10
X1
DRT2-MD16
REMOTE TERMINAL
Detachable
terminal block.
Section 5-5
6
7
0
1
2
3
4
5
6
7
OUT
113