Temperature Input Terminals
OFF Delay
Setting Using the DeviceNet Configurator
1,2,3...
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master can receive notification of the Flag's status.
HH set value
HH Alarm Flag
1. Double-click the icon of the Temperature Input Terminal to be set in the
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
2. Select the Tab Page for the input where the comparator function is to be
set, and select Comparator under the Function Choice heading.
Section 7-6
Hysteresis width
OFF delay
419