Temperature Input Terminals
7. Select the Tab Page for the input that will be adjusted and click the Adjust-
ment Button to open the Adjustment Window.
8. Adjust the lower limit value (lower adjusting value). Input 0 mV from the ref-
erence voltage/current generator (STV) to the Temperature Input Termi-
nal's input terminals. Wait at least 1 minute for the input to stabilize.
9. Click the Fix lower adjusting Value Button. The lower limit adjustment
value will be stored in the Unit.
10. Adjust the upper limit value (upper adjusting value). Input the upper limit
voltage from the reference voltage/current generator to the input terminals
of the input to be adjusted. Refer to the following table for the appropriate
voltage. Wait at least 1 minute for the input to stabilize.
Input type
K1
K2
J1
J2
T
L1
L2
U
N
PL2
Input voltage
50 mV
20 mV
50 mV
20 mV
20 mV
50 mV
20 mV
20 mV
50 mV
50 mV