Total ON Time/Contact Operation Counter
Restrictions
The Monitor Status for Total ON Time or Contact Operation Monitor for All Slaves Read at Once command is
not supported by the following models with manufacturer revision 1.01.
If the command is executed for a model with manufacturer revision 1.01, the values in the response area data
may not be correct.
Applicable Models
Slave name
Remote I/O Terminal with 16 inputs
Remote I/O Terminal with 16 outputs
Environment-resistive Terminal with 8 inputs
Environment-resistive Terminal with 16 inputs
Environment-resistive Terminal with 8 outputs
Sensor Connector Terminal with 16 inputs
Note 1. The (-1) suffix refers to models with PNP.
2. The read command cannot be used with DRT2-ID16(-1) and DRT2-OD16(-1), even if an Expansion
Unit is mounted to the Remote I/O Terminal.
3. Models with manufacturer revision 1.02 or later (lot number 1263E or later) support the Monitor Status
for Total ON Time or Contact Operation Monitor for All Slaves Read at Once command.
Lot numbers:
In the lot number 1263E, 12 = day, 6 = month, 3 = year, and E = factory where product was manufac-
tured. Therefore, 1263E indicates a product manufactured on June 12, 2003.
4. DRT2 Slaves not mentioned in the above table support the Monitor Status for Total ON Time or Con-
tact Operation Monitor for All Slaves Read at Once command, even if the Slaves are models with
manufacturer revision 1.01.
Checking the Manufacturer Revision Code
The manufacturer revision code can be checked by reading it using the EXPLICIT MESSAGE SEND command
(2801) or from the Configurator.
EXPLICIT MESSAGE SEND Command (2801)
Explicit
Service
message
Identity
Read
Reads the iden-
revision
tity revision
Appendix C
Restrictions on Reading
for All Slaves at Once
Function
Service
Code
0E
Model
DRT2-ID16(-1)
DRT2-OD16(-1)
DRT2-ID08C(-1)
DRT2-HD16C(-1)
DRT2-OD08C(-1)
DRT2-ID16S(-1)
Command
Class ID
Instance
ID
01
01
04
Attribute
Data size
ID
---
2 bytes
E.g.,
Response data:
0102: manufac-
turer revision
1.02
Response
539