Temperature Input Terminals
Setting the 1/100 Display Mode
1,2,3...
1,2,3...
386
• Example 1: 850.00 ° C
850 × 100 = 85,000 converted to hexadecimal → 0001 4C08 hex
Rightmost data = 4C08 hex; Leftmost data = 0001 hex
• Example 2: − 200.00 ° C
− 200 × 100 = − 20,000 converted to hexadecimal → FFFF B1E0 hex
Rightmost data = B1E0 hex; Leftmost data = FFFF hex
■ Using the Slave's Default Connection Path
1. Turn ON pin 5 of the Slave's DIP switch. (Select 1/100 display mode.)
2. Turn ON the Master and Slave power supplies. At this point, the Slave will
not be in 1/100 display mode.
3. Double-click the icon of the Slave to be set in the Main Window and open
the Edit Device Parameters Window.
4. Select Temperature Data1 (1/100) or Temperature Data2 (1/100) from
the pull-down menu in the Default Connection Path (In) field. Click the
Download Button and then click the Reset Button to reset the Unit.
■ Using the Master's Connection Path
1. Turn ON pin 5 of the Slave's DIP switch. (Select 1/100 display mode.)
2. Turn ON the Master and Slave power supplies. At this point, the Slave will
not be in 1/100 display mode.
3. Double-click the icon of the Master to be set in the Main Window and open
the Edit Device Parameters Window.
Section 7-6