Transistor Remote Input Terminals With 16 Points And Connectors; Drt2-Id16Ml(X) (Npn) And Drt2-Id16Ml(X)-1 (Pnp) - Omron DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008 Operation Manual

Devicenet slaves
Hide thumbs Also See for DRT2 SERIES DEVICENET SLAVES - OPERATION MANUAL 04-2008:
Table of Contents

Advertisement

Connector Terminals with Transistors
Dimensions (DRT2-MD16S and DRT2-MD16S-1)
5-6-5
Transistor Remote Input Terminals with 16 Points and
Connectors: DRT2-ID16ML(X) (NPN) and DRT2-ID16ML(X)-1 (PNP)
Input Specifications
SHT O
MS
NS
SHT 1
NODE ADDRESS
50
IN 0-7
OUT 0-7
Two, 4.2 dia. or M4 mounting holes
88±0.2
Item
Model
Internal I/O common
Input points
ON voltage
OFF voltage
OFF current
Input current
ON delay time
OFF delay time
Max. simultaneously ON
input points
Number of circuits
Note All 16 inputs can be ON simultaneously if the Remote I/O Terminal is mounted
facing up, but sufficient space will need to be allowed between Units depend-
ing on the ambient temperature. Refer to the Dimensions diagram on
page 156 for details.
95
0
1
2
3
4
5
6
7
IN
0
1
2
3
4
5
6
7
OUT
DRT2-ID16ML(X)
NPN
16 points
17 V DC min. (between
each input terminal and V)
5 V DC max. (between
each input terminal and V)
1.0 mA max.
6.0 mA max./point at 24 V DC
3.0 mA min./point at 17 V DC
1.5 ms max.
1.5 ms max.
16 points (See note.)
16 points with one common
Section 5-6
33.3
3
36.8
Specification
DRT2-ID16ML(X)-1
PNP
17 V DC min. (between
each input terminal and G)
5 V DC max. (between
each input terminal and G)
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Devicenet drt2-id08Devicenet drt2-id08-1Devicenet drt2-id16-1Devicenet drt2-od16Devicenet drt2-od08Devicenet drt2-md16 ... Show all