Functions of General-purpose Slaves and Environment-resistive Slaves
Setting Using the
DeviceNet
Configurator
1,2,3...
■ Measurement for ON time of 0.5 s:
In Fig. 1, the actual ON time is 0.5 s × 3 = 1.5 s. The measurement will be
taken once during this ON time, so the total ON time will be measured as 1 s.
Reading taken approximately every second.
ON
OFF
0.5 s
Figure 1
In Fig. 2, the actual ON time is 0.5 s × 3 = 1.5 s. The reading will be taken
twice during this ON time, so the total ON time will be measured as 2 s.
Reading taken approximately every second.
ON
OFF
0.5 s
Figure 2
■ Measurement for ON time of 1.5 s:
In Fig. 3, the actual ON time is 1.5 s × 2 = 3 s. The measurement will be taken
four times during this ON time, so the total ON time will be measured as 4 s.
Reading taken approximately every second.
ON
OFF
1.5 s
Figure 3
The method used to set values from the DeviceNet Configurator (Ver. 2.20 or
later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
2. From the Main Window, open the Network Configuration Window and dou-
ble-click or click the right mouse button over the icon of the DRT2-series
Smart Slave to be set. Select Parameter and Edit to display the Edit De-
vice Parameters Window.
From the Maintenance Mode Window, click the right mouse button over the
icon of the DRT2-series Smart Slave to be set. Select Parameter and Edit
to display the Edit Device Parameters Window.
Section 4-3
67