Continuous Mode Speed Control
Pulse output will continue until it is stopped from the program.
Note Pulse output will stop immediately if the CPU Unit is changed to PROGRAM mode.
Opera-
Purpose
Application
tion
Starting
To output
Accelerating the
pulse
with
speed (frequency)
output
specified
at a fixed rate
acceleration
and speed
Changing
To change
Changing the
settings
speed
speed smoothly
smoothly
during operation
Changing the
speed in a polyline
curve during
operation
Decelerating to a
stop
Stopping
To stop
Immediate stop
pulse
pulse output
output
To stop
Decelerating to a
pulse output
stop
smoothly
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Frequency changes
Pulse frequency
Target frequency
Acceleration/
deceleration
rate
Present frequency
Execution of
ACC(888)
Pulse frequency
Target frequency
Acceleration/
deceleration
rate
Present frequency
Execution of
ACC(888)
Pulse frequency
Acceleration rate n
Target frequency
Acceleration
rate 2
Acceleration
rate 1
Present frequency
Execution of ACC(888)
Execution of ACC(888)
Execution of ACC(888)
Pulse frequency
Acceleration/deceleration rate 1
Present
frequency
Target
frequency = 0
Execution of ACC(888)
Execution of ACC(888)
Execution of ACC(888)
(target frequency = 0)
Pulse frequency
Present frequency
Execution of ACC(888)
Pulse frequency
Acceleration/deceleration
Present frequency
rate (value set when starting)
Target frequency = 0
Execution of ACC(888)
Execution of ACC(888)
Description
Outputs pulses and
changes the frequency at
a fixed rate.
Time
Changes the frequency
from the present
frequency at a fixed rate.
The frequency can be
accelerated or
decelerated.
Time
Changes the
acceleration or
deceleration rate during
acceleration or
deceleration.
Time
The acceleration/
deceleration rate is
changed while
decelerating.
Acceleration/
deceleration rate 2
Note If the target
frequency is set to
Time
0 pps, the current
acceleration/
deceleration rate
will be used.
Immediately stops pulse
output.
Time
Execution of INI(880)
Decelerated pulse output
to a stop.
Note If the target
frequency of the
second ACC(888)
instruction is 0 pps,
Time
the
acceleration/decel
eration rate from
the first ACC(888)
instruction will be
used.
3. Instructions
Procedure/
instruction
ACC(888)
(Continuous)
ACC(888) or
SPED(885)
(Continuous)
3
ACC(888)
(Continuous)
ACC(888)
(Continuous)
ACC(888)
(Continuous)
ACC(888)
(Continuous)
ACC(888)
(Continuous)
ACC(888)
(Continuous,
target
frequency of
0 pps)
ACC(888)
(Continuous)
INI(880)
(Continuous)
ACC(888)
(Continuous)
ACC(888)
(Continuous,
target
frequency of 0
pps)
769

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CJ - INSTRUCTIONS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents

Save PDF