3. Instructions
Bit Address Found Flag
1: Bit address found
R: D300
R+1: D301
R+2: D302
R+3: D303
R+4: D304
R+5: D305
R+6: D306
R+7: D307
R+8: D308
R+9: D309
R+10: D310
Setting the Monitoring Time with the Teaching Function
The monitoring time can be set automatically with the teaching function when a word address has been
specified for T.
Execution
condition
300.00
To start the teaching function, turn ON A598.00 (the FPD Teaching Bit). While A598.00 is ON,
FPD(269) measures how long it takes for the diagnostic output (CIO 200.00) to go ON after the
execution condition (CIO 300.00) goes ON. If the measured time exceeds the monitoring time in T, the
measured time is multiplied by 1.5 and that value is stored in T as the new monitoring time.
FPD Teaching Bit
Execution condition
Diagnostic output
t
: Initial setting in T
s
t
: Measured time
a
t'
: New setting in T after teaching
s
(When t
> t
, t'
a
s
s
1038
FAL number = 10
Diagnostic output mode = 8 (bit address and message output)
Input type
0: Normally open
Not used.
30
30
30
2D
54
25
25
00
00
The teaching function
can set the monitoring
T
D200
time in T automatically.
R
D300
200.00
Diagnostic output
A598.00
CIO 300.00
CIO 200.00
Measured time: t
Teaching
= t
1.5)
a
31
Contains bit address in ASCII.
30
(100.00 is converted to ASCII.)
30
30
25
F4
User-set FAL error message output to a
00
Peripheral Device by the time monitoring
00
function. The Peripheral Display will show
00
the following: 100.00-0 ERROR.
a
CS/CJ/NSJ Series Instructions Reference Manual (W474)
No error generated.
t'
(t
1.5)
s
a