Bit Address and Message Output (C=8@@@)
When the leftmost digit of C is set to 8, the ASCII address of the input bit is output to R+2 to R+4. R
contains two flags which indicate whether an input bit has been found and whether it is used in a
normally open or normally closed input condition.
15
14
13
R
Input type
0: Normally open
1: Normally closed
Bit Address Found Flag
0: Not found yet
1: Bit address found
15
R+1
15
D+2
D+3
D+4
Register words R+2 through R+5 would have the following values for W51115.
15
R+2
W
R+3
1
R+4
1
15
D+5
2D (hexadecimal)
D+6 to D+9
The user can store an ASCII message in register words R+6 to R+10. This message will be displayed
on the Programming Device if a non-fatal error is generated by the time monitoring function. Mark the
end of the message with the null character (00 hexadecimal).
15
8
R+6
R+7
R+8
R+9
R+10
CS/CJ/NSJ Series Instructions Reference Manual (W474)
0
Not possible to use.
0
Not possible to use.
8
7
0
Stores the bit number
A0.00 to A959.15
H0.00 to H511.15
W0.00 to W511.15
0.00 to 6143.15
TK0 to TK1023
_T0000 to _T4095
_C0000 to _C4095
Note The "_" represents an ASCII space.
5
1
Bit address written in ASCII
5
8
7
0
Input type (hexadecimal)
30: Normally open
31: Normally closed
7
0
3. Instructions
3