Hardware Installation and Reference Guide
For the cable terminals fastened by screw threads, tighten the bolt or screw and take cable retention
measures, as shown in
Figure 7-12
Cable Fastening
Hard power cords should be fastened in the terminal connection area to prevent stress on terminal connection
and cable.
Do not use self-tapping screws to fasten terminals.
Power cords of the same type and in the same cabling orientation should be bundled up into one cable
bundle. The power cords in the bundle should be clean and straight.
Bundle up cables by using cable ties.
Table 7-3
Cable Bundling
Cable Bundle Diameter
10 mm (0.39 in.)
10 mm to 30 mm (0.39 in. to 1.18 in.)
30 mm (1.18 in.)
No knot is allowed in cabling or bundling.
For wiring terminal blocks (such as circuit breakers) with insulated terminals, the metal part of the insulated
terminal should not be exposed outside the terminal block during assembling.
Figure
7-12.
Distance between Every Binding Point
80 mm to 150 mm (3.15 in. to 5.91 in.)
150 mm to 200 mm (5.91 in. to 7.87 in.)
200 mm to 300 mm (7.87 in. to 11.81 in.)
68