Danfoss VACON 1000 Operating Manual page 95

Fieldbus options
Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000 Fieldbus Options
Operating Guide
Category
Error code
H'11010115
H'11010116
H'1101011E
H'1101011F
H'11010120
H'11010121
H'11010122
H'11010123
H'11010124
H'11010125
H'11010126
H'11010129
H'11010132
Data Exchange
H'12010100
Setup Error
H'12010106
H'12010110
H'12010111
H'12010113
Danfoss A/S © 2023.09
Description
The device type parameters in
the EDS file are mismatched.
The revision parameters in the
EDS file are mismatched.
The direction parameters in the
EDS file are mismatched.
The fixed/variable output flag
in the EDS file is mismatched.
The fixed/variable input flag in
the EDS file is mismatched.
The output priority in the EDS
file is mismatched.
The input priority in the EDS file
is mismatched.
The output connection type pa-
rameters in the EDS file are mis-
matched.
The input connection type pa-
rameters in the EDS file are mis-
matched.
The redundant ownership out-
put parameters in the EDS file
are mismatched.
The configuration size parame-
ters in the EDS file are mis-
matched.
The configuration path param-
eters in the EDS file are mis-
matched.
The EDS file does not support
Null forward open.
I/O connections duplicated
Scanner ownership of I/O con-
nections conflicts
Incorrect adapter configuration
Adapter RPI not supported
Insufficient I/O connections
Troubleshooting
Check if the system has created the I/O connections.
Change the connection type to Listen Only.
Check the scanner owner.
Reconfigure the invalid scanner.
Change the connection to multicast.
Check the I/O connection status.
Activate the I/O connections again.
Check the RPI for the adapter.
Check if the number of connections exceeds the limit.
Reduce the number of the product connections.
AQ454734633756en-000101 / 172K1112 | 95