VACON® 1000 Fieldbus Options
Operating Guide
#
Parameter name
bit5:Encoder Abnormal
bit6:Input Over Current(Hardware)
bit7:Output Over Current(Hardware)
bit8:External Fault
bit9:Current Sensor Power Fault
bit10:Fault Code Query Failure
bit11:Bypassed Cell Quantity Over Limit
bit12:Power On With MCB Signal Loss
bit13:Reserved
bit14:Transformer Temperature Sensor Loss
bit15:Reserved
3
bit0:Auto Tuning Failure
bit1:Flying Start Failure
bit2:Automatic Restart Failure
bit3:Synchronous Transfer Failure
bit4:Reserved
bit5:Reserved
bit6:Failure Of Motor Selection
bit7:LVRT Failure
bit8:Reserved
bit9:Bypass Derating Failure
bit10:Input Current Sampling Fault
bit11:Output Current Sampling Fault
bit12:Power Cell Overload
bit13:Software And Hardware Versions Are Inconsistent
bit14:Software And Hardware Versions Are Incompatible
bit15:Switch of Synchronous transfer Action Failure
4
bit0: External/Customer Control Power Loss
bit1:Internal Control Power Loss
bit2:PLC Battery Voltage Low
bit3:UPS undervoltage
bit4:Control Power Loss Overtime
bit5:UPS undervoltage Overtime
bit6:HV Cabinet Door Open
bit7:Air Filter Clogged
bit8:Cooling Fan Abnormal
bit9:Fan Internal Power Loss
bit10:Fan External Power Loss
bit11:Transformer T31 overtemperature Alarm
bit12:Transformer T31 overtemperature Fault
bit13:Transformer T31 Temperature Sensor Loss
bit14:Emergency Stop
bit15:Remote Emergency Stop
5
bit0:PLC-DSP Communication Failure
bit1:PLC-HMI Communication Failure
bit2:DSP Fault(X1.1)
bit3:DSP Alarm(X1.2)
20 | Danfoss A/S © 2023.09
Modbus
Function
Data
Address
Code
Format
275
3(Read)
Word
276
3(Read)
Word
277
3(Read)
Word
AQ454734633756en-000101 / 172K1112
Modbus RTU/TCP
Data description
"1" is fault, "0" is ok