Danfoss VACON 1000 Operating Manual page 75

Fieldbus options
Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000 Fieldbus Options
Operating Guide
-
When the switch is turned on, the terminal resistance is connected.
-
When the switch is turned off, the terminal resistance is disconnected.
485+
485-
485 Device 1
485+
485-
485 Device 2
.
.
.
485+
485-
485 Device N
Illustration 35: RS485 Network Topology
7.3.5 Ethernet Terminals
The Ethernet interface uses an RJ45 interface and follows the IEEE802.3u 100BASE-T standard. The pinout (standard Ethernet signal)
is defined in the following table.
Table 54: Ethernet Terminal Specification
Pin
Signal Description
S1
TXD+, Transmit Data+
S2
TXD-, Transmit Data-
S3
RXD+, Receive Data+
S4
Bi-directional Data+
S5
Bi-directional Data-
S6
RXD-, Receive Data-
S7
Bi-directional Data+
S8
Bi-directional Data-
7.4 Quick Start Guide
The gateway configuration in the SST-TS-CFG software must be consistent with the configuration of the PROFINET Master station.
Device IP Address
Device Name
The type and order of the "PROFINET Configuration Module".
Procedure
1.
Connect the network port of the gateway to the PC with a network cable for downloading the configuration.
Another network port can be connected to PROFINET master equipment such as PLC for data communication.
2.
Connect the serial port of the gateway to the serial device for communication with the serial port device.
3.
Connect the gateway power supply and power on.
Danfoss A/S © 2023.09
1
D+
2
D-
3
GND
AQ454734633756en-000101 / 172K1112 | 75