Danfoss VACON 1000 Operating Manual page 87

Fieldbus options
Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000 Fieldbus Options
Operating Guide
-
EN
bit1:VFD running
bit2:Reserved
bit3: Local/Remote
bit4:Fault
bit5:Alarm
bit6:Reserved
bit7:MCB closed
bit8:Reserved
bit9:MCB Close allowed
bit10:Reserved
bit11:Reserved
bit12:Reserved
bit13:Reserved
bit14:Reserved
bit15:Reserved
Command
1
VFD start
2
VFD coast stop
3
VFD ramp stop
4
System reset
5
Reference speed (RPM)
6
Reference Frequency (0.01 Hz)
System alarm/fault
1
bit0:Input overcurrent (Software)
bit1:Input Phase Loss
bit2:Input Power Loss
bit3:Input undervoltage
bit4:Input overvoltage
bit5:Input Grounding
bit6:Input Sequence Fault
bit7:Reserved
bit8:Output overcurrent (Software)
bit9:Output Over Load
bit10:Output Phase Loss
bit11:Output Grounding
bit12:Output Phase Imbalance Alarm
bit13:Output Phase Imbalance Fault
bit14:Output Under Load
bit15:Electronic Motor Thermal Protection
2
bit0:Motor Stall
Danfoss A/S © 2023.09
Address
Data For-
Data description
mat
D0
Word
bit0: 2 s Rising edge
pulse
D0
Word
bit1: 2 s Rising edge
pulse
D0
Word
bit2: 2 s Rising edge
pulse
D0
Word
bit3: 2 s Rising edge
pulse
D1
Word
D2
Word
D272
Word
"1" is fault,"0" is ok
D273
Word
"1" is fault,"0" is ok
AQ454734633756en-000101 / 172K1112 | 87