VACON® 1000 Fieldbus Options
Operating Guide
Table 42: LSS Inquires Vendor-ID, Product-code, Revision-number, and Serial Number
Send:
7E5
5A 00 00 00 00 00 00 00
Receive:
7E4
5A 1B 00 00 00 00 00 00
Send:
7E5
5B 00 00 00 00 00 00 00
Receive:
7E4
5B 04 00 00 00 00 00 00
Send:
7E5
5C 00 00 00 00 00 00 00
Receive:
7E4
5C 1B 00 00 00 00 00 00
Send:
7E5
5D 00 00 00 00 00 00 00
Receive:
7E4
5D xx xx xx xx 00 00 00
Table 43: LSS Switches Selected State of Node
Send:
7E5
40 1B 00 00 00 00 00 00
Send:
7E5
41 04 00 00 00 00 00 00
Send:
7E5
42 00 04 00 00 00 00 00
Send:
7E5
43 xx xx xx xx 00 00 00
Receive:
7E4
44 01 00 00 00 00 00 00
5.7 Troubleshooting
Table 44: Troubleshooting
Number
Description
1
ERR red indicator light on in operation
state
2
ERR red indicator light blinking in opera-
tion state
3
ERR red indicator light off in operation
state, but sending/receiving of CAN error
4
ERR red indicator light blinking occasion-
ally
5
ERR red indicator light always blinking, no
data sending to Modbus
6
Serial indicators (TX) green blinking
7
Serial indicators (TX) green blinking
Danfoss A/S © 2023.09
→ Read Vendor-ID
→ Success (Vendor-ID=0X1B)
→ Read product-code
→ Success (product-code=0X04)
→ Read revision-number
→ Success
→ Read serial-number
→ Success xx means product serial number
→ Match VENDOR_ID
→ Match PRODUCT_CODE
→ Match REV_NUMBER
→ Match SERIAL_NUMBER
→ Success 01 means configuration mode
Suggestions
CAN bus BUS OFF or sending/receiving error counter exceed alarm val-
ue.
Check whether CAN baud rate of gateway is the same as in other nodes
on CAN network.
Need a terminal resistance on CAN network or the gateway has no con-
nection to CAN network.
Need a terminal resistance on CAN network or the node connected with
gateway fail.
There is error frame form CAN network, but does not affect communica-
tion.
Check the baud rate of all the nodes on the CAN network. If they are all
the same, change a lower baud rate and try again.
Modbus slave address on Modbus network is not the same with the
gateway ready to read
Modbus slave device on Modbus network does not support the function
code configured in the gateway