VACON® 1000 Fieldbus Options
Operating Guide
PROFIBUS DP
For example, set frame type to "delimiter", "start character" is 0xff, "end character" is 0xfe, "time interval between characters" is
10 ms, and input and output bytes length of PROFIBUS master is 8 bytes. The PROFIBUS DP module receives the data correctly only
if the serial devices send FF xx xx xx FE with no timeout. The data are all HEX.
The data length that the PROFIBUS DP module sends to the serial device depends on the data value in the frame that PROFIBUS
sends to the PROFIBUS DP module.