VACON® 1000 Fieldbus Options
Operating Guide
Code (HEX)
13
15
17
Table 39: Index Values for Baud Rates
Baud Rate [kbps]
1000
800
500
250
125
100
50
20
10
Table 40: LSS Switches Slave Node ID (Default Factory Node ID 0X7F, Set Node ID 0X44)
Send:
00
Send:
7E5
Send:
7E5
Receive:
7E4
Send:
7E5
Receive:
7E4
Send:
7E5
Send:
00
Receive:
744
NewNode ID will take effect after reset or power off and power on the gateway.
Table 41: LSS Switches Slave Baud Rate
Send:
7E5
Send:
7E5
Receive:
7E4
Send:
7E5
62 | Danfoss A/S © 2023.09
Function
Configure new baud rate
Start new baud rate
Save LSS configuration
80 7F
04 01 00 00 00 00 00 00
11 44 00 00 00 00 00 00
11 00 00 00 00 00 00 00
17 00 00 00 00 00 00 00
17 00 00 00 00 00 00 00
04 00 00 00 00 00 00 00
81 7F
00
04 01 00 00 00 00 00 00
13 00 02 00 00 00 00 00
13 00 00 00 00 00 00 00
15 10 00 00 00 00 00 00
Index Value
0
1
2
3
4
5
6
7
8
→ Push node to Pre-operational state
→ Set configuration mode
→ Set node address 0x44
→ Success
→ Store configuration
→ Success
→ Waiting state
→ Reset node
→ New boot-up message
→ Set configuration mode
→ Set 500 kBits
→ Success
→ switch on 500 kBits
AQ454734633756en-000101 / 172K1112