Danfoss VACON 1000 Operating Manual page 96

Fieldbus options
Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000 Fieldbus Options
Operating Guide
Category
Error code
H12010119
H'12010127
H'12010128
H'1201012D
H'1201012E
H'12010204
H'12010302
H'12010315
8.5.3 Application Error
Table 62: Application Error Description
Category
Error Code
EtherNet/IP Error
H'00010203
96 | Danfoss A/S © 2023.09
Description
The connection of non-Listen
only is not established.
Incorrect adapter input size
Incorrect adapter output size
Consumed Tag does not exist.
Produced Tag does not exist.
I/O connection connecting
timeout
Network bandwidth NOT avail-
able for data
Incorrect adapter input/outpu-
tinstance
Description
I/O connection timeout
Troubleshooting
Check if the system has created the I/O connections.
Check the scanner I/O connection status.
Check the module number and the product setup file,
and see if they match.
Check the output size in the connection parameters.
Check if the parameters in the Consumed tag are set cor-
rectly.
Check if the parameters in the Produced tag are set cor-
rectly.
No response from the adapter; check if the power and
the network connection for the adapter are working
properly.
Check the I/O connection limit between the scanner and
the adapter.
Increase the RPI value or reduce the number of connec-
tions.
Check the module number and the product setup file,
and see if they match.
Troubleshooting
Check the network connection status.
Check if the module is working properly.
Increase the RPI value.