VACON® 1000 Fieldbus Options
Operating Guide
Use mode switch to move to the configuration mode.
•
After powering on, the LED display shows the PROFIBUS DP address when acting as a slave.
•
Press the button for 5 s, and the LED display starts to blink.
•
Click the button once, and the LED display enters configuration mode.
•
Connect to the serial port of a PC through any one of the RS232/RS485/RS422 serial ports on the PROFIBUS DP module, and
finish configuration uploading and downloading.
•
After downloading, press the button for 2.5 s to enter the normal communication mode.
•
To finish uploading and downloading, connect the USB port of the PROFIBUS DP module to a PC. Select whether to enter into
the communication mode according to hints from the software.
Modifying the PROFIBUS DP address
•
After powering on, the LED display shows the PROFIBUS DP address when acting as a slave.
•
To enter the PROFIBUS DP address modifying state, double-click the button.
-
The high bit of the DP address starts blinking and low bit is always on.
-
To make the number increase by one, press the button once.
•
To switch to the setting state for the low bit, press the button for 2.5 s.
-
When setting the low bit state, the LED for the high bit is always on and low bit is blinking.
-
To make the number increase by one, press the button once.
•
To save the new address and enter the normal communication state, press the button for 2.5 s.
-
The high bit and low bit of the LED display are always on.
If there is no operation of the button for over 10 s when changing the DP address, the LED display automatically returns to the
normal communication state. If this happens, the previous operations are invalid.
Press button
for 5 s
LED display
blinking
Click button
LED display on:
Configuration
mode
Press button
for 2.5 s
Illustration 8: Flowchart of the LED Display States
Danfoss A/S © 2023.09
Power off:
LED display off
Power on
Normal communication state:
LED display high/low bits always on.
PROFIBUS DP address shown.
Double-click
button
High bit setting state:
LED high bit blinking.
LED low bit always on.
Press button
for 2.5 s
Low bit setting state:
LED high bit always on.
LED low bit blinking.
Press button
for 2.5 s
Click button
LED high bit
increased by 1
Click button
LED low bit
increased by 1