Modbus Data Mapping; Mvd Input Parameters; Mvd Output Parameters; Transformer Temperature - Danfoss VACON 1000 Operating Manual

Fieldbus options
Hide thumbs Also See for VACON 1000:
Table of Contents

Advertisement

VACON® 1000 Fieldbus Options
Operating Guide
Function (dec)
Function (hex)
4
4
5
5
6
6
15
F
16
10
23
17
Broadcasting is not supported in TCP. Broadcast is supported with function codes 06 and 16 in RTU.
The address ranges of the different function codes are often not relevant to the user and can be ignored. The targeted information
type (coil, register, and so on) can be selected separate from the address.

3.3.4 Modbus Data Mapping

3.3.4.1 MVD Input Parameters

Table 10: MVD Input Parameters
Number
Parameter
1
Input current (A)
2
Input voltage (V)
3
Reference speed (RPM)
4
Reference Frequency (0.01 Hz)
5
Input power (kVA)

3.3.4.2 MVD Output Parameters

Table 11: MVD Output Parameters
Number
Parameter
1
Output current (A)
2
Output voltage (V)
3
Output Frequency (0.01 Hz)
4
Output speed (RPM)

3.3.4.3 Transformer Temperature

Table 12: Transformer Temperature
Number
Parameter
1
Transformer temperature T31 A (0.1°C)
2
Transformer temperature T31 B (0.1°C)
3
Transformer temperature T31 C (0.1°C)

3.3.4.4 Digital Output

Danfoss A/S © 2023.09
Modbus Function Name
Read Input Registers
Write Single Coils
Write Single Register
Write Multiple Coils
Write Multiple Registers
Read/Write Multiple Registers
Modbus Address
9004
9002
9101
9103
9006
Modbus Address
9005
9003
9010
9008
Modbus Address
9011
9012
9013
TCP/RTU
Access type
TCP and RTU
Register (16 bit)
TCP only
Discrete (1 bit)
TCP and RTU
Discrete (1 bit)
TCP only
Discrete (1 bit)
TCP and RTU
Register (16 bit)
TCP and RTU
Register (16 bit)
Function Code
Data Format
3 (Read)
Word
3 (Read)
Word
3/6 (Read/Write)
Word
3/6 (Read/Write)
Word
3 (Read)
Word
Function Code
Data Format
3 (Read)
Word
3 (Read)
Word
3 (Read)
Word
3 (Read)
Word
Function Code
Data Format
3 (Read)
Word
3 (Read)
Word
3 (Read)
Word
AQ454734633756en-000101 / 172K1112 | 27
Modbus RTU/TCP
Address range (hex)
30000- 3FFFF
00000- 0FFFF
40000- 4FFFF
00000- 0FFFF
40000- 4FFFF
40000- 4FFFF
Data description
MUL100
Data description
DIV100
Data description
DIV 10
DIV 10
DIV 10