VACON® 1000 Fieldbus Options
Operating Guide
#
Parameter name
11
Reserved
12
bit0:External Fault
bit1:Arc Flash Relay Error
bit2:Arc Flash Relay Tripped
bit3:Transformer T32 overtemperature Alarm
bit4:Transformer T32 overtemperature Fault
bit5:Transformer T32 Temperature Sensor Loss
bit6:Filter Cabinet overtemperature
bit7:Reactance Cabinet overtemperature
bit8:Motor Winding overtemperature
bit9:Motor Winding Ultra overtemperature
bit10:Motor Bearing overtemperature
bit11:Motor Bearing Ultra overtemperature
bit12:Motor Temperature Sensor Loss
bit13:Control Cabinet Low Temperature Alarm, MCB Close For-
bidden
bit14:Control Cabinet Low Temperature Fault
bit15:Control Cabinet Temperature Sensor Loss
13
bit0:Control Cabinet overtemperature Alarm
bit1:Control Cabinet overtemperature Fault
bit2:Control Cabinet Temperature Sensor Loss
bit3:Control Cabinet cooling Fan Power Loss
bit4:PLC Module Error
bit5:PLC Remote Module Error
bit6:PID Analog Feedback Loss
bit7:Reserved
bit8:Control Cabinet Low Temperature Alarm, Start Forbidden
bit9:Remote Signal Select Motor Failure
bit10:Remote Signal Select Motor Direction Failure
bit11:Remote Signal Select Motor Speed Ramps Failure
bit12:Control Cabinet Low Temperature Alarm
bit13:Reserved
bit14:Reserved
bit15:Reserved
14
bit0:KM42 Abnormal Open (DSP)
bit1:KM42 Abnormal Close (DSP)
bit2:KM43 Abnormal Open (DSP)
bit3:KM43 Abnormal Close (DSP)
bit4:Reserved
bit5:Reserved
bit6:Reserved
bit7:Reserved
bit8:Reserved
bit9:Reserved
bit10:Reserved
bit11:Reserved
bit12:Reserved
Danfoss A/S © 2023.09
Modbus
Function
Data
Address
Code
Format
283
3(Read)
Word
284
3(Read)
Word
285
3(Read)
Word
286
3(Read)
Word
AQ454734633756en-000101 / 172K1112 | 23
Modbus RTU/TCP
Data description
"1" is fault, "0" is ok
"1" is fault, "0" is ok
"1" is fault, "0" is ok